It is a cold morning in Locust Grove. You arrive before opening and find the building at 62°F instead of the 70°F on the thermostat. The rooftop heat pump is running, but the air from the vents feels cool. Your phone starts ringing.
It is easy to assume the system has failed. But nothing may be broken. Cold weather does not create most heat pump problems; it exposes them. There is a real difference between a heat pump working hard and a heat pump failing, and knowing what to expect can help you decide when it is time to call for service.
“Cold weather doesn't create most heat pump problems. It exposes them. I'd rather we find the weak spot in October than have you find it at six in the morning on the coldest day of the year.”
Manuel, owner of A-Advanced Home Services
How a commercial heat pump heats your building
A heat pump moves heat from the outdoor air into your building. It does not burn fuel to create heat. Even when the outdoor air feels cold, it still contains some heat energy for the system to move indoors.
As the temperature drops, though, the heat pump has to work harder. Its heating capacity and efficiency decline, and its run times get longer. That change is expected; it does not automatically mean the unit is failing.
The balance point is the outdoor temperature at which the heat pump alone can no longer keep up with the building’s heat loss. Below that point, backup heat, often electric strip heat in an all-electric system, helps meet the demand. The balance point varies with the equipment, building, outdoor air and ventilation load, and control settings.

What you may see and hear when it gets cold
During cold weather, a commercial heat pump may behave differently from a gas furnace. These signs can be normal:
- Longer run times: The system may run for much of the day as it works to replace heat leaving the building.
- Air that feels warm, not hot: Heat pump supply air is often cooler to the touch than furnace air, even when the system is heating properly.
- A defrost cycle: Frost can form on the outdoor coil. During defrost, the outdoor fan may stop and a cloud of steam or vapor may rise from the coil. The unit should return to heating afterward.
- Auxiliary heat: Electric strip heat may come on during defrost or when the building is recovering from a nighttime temperature setback.
A defrost cycle should clear frost so the unit can keep transferring heat. If defrost controls fail to start or end the sequence correctly, ice can accumulate and reduce heating. Persistent ice is not the same as a brief, normal defrost cycle.
Signs that deserve a service call
Contact a technician if you notice any of the following:
- Ice that remains on the outdoor coil for hours or builds into a solid block.
- The indoor fan running for a long stretch with no heat at all.
- A breaker that trips, a burning smell, or water or ice inside the building or on the roof curb.
- Defrost cycles that seem to repeat every few minutes.
- Refrigerant lines that are frosted, or long run times and cold supply air paired with an unusually high electric bill.
A reversing valve or defrost-board fault can interfere with heating and defrost operation. Low refrigerant charge can also contribute to long run times, weak heat and higher electrical use. These conditions require proper diagnosis, not a guess based on how the air feels.
Two other issues can look like a failed heat pump but have a different cause:
- Restricted airflow: A dirty filter or blocked coil can make the system work harder and deliver less heat.
- Controls or scheduling problems: A thermostat or building-controls schedule may still be set for cooling, or an aggressive overnight setback may call for a difficult recovery before opening.

Why a cold snap can affect your electric bill
Many commercial electric bills include a demand charge based on the highest level of electricity use during the billing period. Electric strip heat can be the largest electrical draw in many heat-pump buildings. When a cold snap lines up with a defrost problem, poorly staged backup heat or a rapid morning warm-up, the added demand may show up on the bill.
Proper staging helps bring backup heat on when it is needed, rather than unnecessarily. Clean coils support heat transfer, too. If demand jumps, the answer is not automatically a new building or a new system. Maintenance and control settings are sensible places to investigate first.
What a commercial heating service visit checks
A commercial heating service visit looks at the equipment and the conditions affecting its operation. Depending on your system, a technician may check:
- Filter and coil condition.
- Refrigerant charge and pressures against equipment specifications.
- Defrost board, sensors and reversing valve operation.
- Electric strip heat, sequencers and contactors.
- Airflow and static pressure.
- Economizer and outside-air damper position. A damper bringing in too much outside air during winter can contribute to comfort complaints.
- Belt and blower condition.
- Thermostat and building-controls schedules.
- Roof curb and drain pan condition.
- Disconnect and wiring condition.
Heat pumps and packaged rooftop units are both within the scope of A-Advanced’s commercial HVAC services. Regular HVAC maintenance can also help identify a concern before a busy winter day makes it urgent.

December schedules can change how your system runs
Holiday closures, reduced occupancy and overnight setbacks all change a building’s heating pattern. When staff return after a closure or setback, the system may need more time to bring the space back to its occupied temperature. In many local buildings, heat pumps are the only heat source, so a system failure can mean no heat for tenants or staff.
A service agreement can put scheduled check-ups on the calendar before the coldest weeks instead of after a breakdown. A-Advanced offers Silver, Gold and Platinum options. Ask which schedule and coverage fit your equipment and building needs.
Repair or replace? Consider the building’s needs
A repair may be the practical choice when the equipment is serviceable and the issue can be corrected. Replacement may be worth discussing when age, parts availability or recurring problems make continued repairs less suitable.
The building’s setup matters, too. Is one unit out of ten affected, or is it the only unit serving the space? How important is the space to your operations? What refrigerant type does the equipment use, and are the parts needed for repair available?
As a Trane dealer, A-Advanced can discuss replacement options, new system installation and financing for a new system or service. The right decision depends on your equipment, budget and operating needs, not a one-size-fits-all rule.
Get help with commercial heat pump service
If you are looking for commercial HVAC service or HVAC repair in Louisa, Locust Grove, or Orange, VA, call (888) 281-2243. A-Advanced Home Services provides commercial HVAC service and repair for all brands, with a reputation for doing the job right the first time. If you need urgent help, 24/7 emergency service is available.
If you manage a building in Gordonsville or Spotsylvania, we cover those too, and our expert technicians will walk you through what they find before you spend anything. Senior customers receive 10% off.
Call (888) 281-2243 or visit a-advanced.com. A-Advanced Home Services is located at 7240 Zachary Taylor Hwy, Mineral, VA 23117. Virginia contractor license VA#2705106822.